LH100 substation intelligent comprehensive dehumidification system Introduction:
The LH100 substation intelligent comprehensive dehumidification system adopts a digital temperature and humidity transmitter array to monitor the average temperature and humidity inside the distribution room, cable trench, and outdoor. Based on this, the algorithm recommended by the World Meteorological Organization and the national military standard GJB1172.1 is used to calculate the air moisture content (water vapor partial pressure) and dew point temperature. The above basic data and calculation data are the basis for the power distribution and control unit to control various execution equipment (including dehumidifiers, cable trench fans, cabinet top and busbar bridge fans, ventilation fans or accident fans, electric windows, etc.). When humidity, temperature, water vapor partial pressure, etc. reach the upper limit of the set value, it will start
Execute equipment in the corresponding area; If it is below the lower limit of the set value, stop the corresponding execution equipment in the area; Technical parameters:
Temperature and humidity transmitter
Power supply: DC24 V/100mA
Sensor type: Imported digital temperature and humidity sensitive component
Accuracy: Temperature ≤ ± 0.5 ℃ @ 25 ℃, ± 3% RH @ 20%~80% RH/25 ℃ Temperature range: -40~80 ℃
Humidity range: 0-100% RH
Communication interface: Standard MODBUS protocol/485 interface
Power distribution and control unit
Power capacity: AC380 V/220 V-63A
Distribution circuit number: 1 total air switch incoming line+9 air switch feeders (including 7 with contactor control) Central processor: 32-bit, RISC, 400 MHz
Working temperature range: -20 ℃~45 ℃/indoor use, where HMI is 0-50 ℃
Data recording cycle: 1 minute
Communication interface/protocol: RS485/MODBUS, capable of communicating with backend computers
Dehumidifier
Dehumidifier power supply: AC380 V/50Hz Dehumidifier configuration: 2-4 units
Single dehumidification capacity: configuration quantity x 210 liters/day
Single dehumidifier power: configuration quantity x 3150W
Applicable area of a single dehumidifier: 200-300m ² (3 meters high)
Electric windows
Power supply: 220VAC or DC24 V-50 W per window opener;
Push pull force: approximately 450N;
Operating speed: approximately 15mm/s; Operating speed: approximately 15mm/s;
Introduction:
The LH100 substation intelligent comprehensive dehumidification system adopts a digital temperature and humidity transmitter array to monitor the average temperature and humidity inside the distribution room, cable trench, and outdoor. Based on this, the algorithm recommended by the World Meteorological Organization and the national military standard GJB1172.1 is used to calculate the air moisture content (water vapor partial pressure) and dew point temperature. The above basic data and calculation data are the basis for the power distribution and control unit to control various execution equipment (including dehumidifiers, cable trench fans, cabinet top and busbar bridge fans, ventilation fans or accident fans, electric windows, etc.). When humidity, temperature, water vapor partial pressure, etc. reach the upper limit of the set value, it will start
Execute equipment in the corresponding area; If it is below the lower limit of the set value, stop the corresponding execution equipment in the area;