1
Item | Index | |||
Measuring range | temperature | -40.0°C~+99.9°C | ||
humidity | 20%RH~90%RH | |||
Precision | temperature | ±3°C | ||
humidity | ±5%RH | |||
Transmitting output | DC4-20mA or DC0-20mA | |||
Control parameter setting range | Heating for warm-up | -40.0°C~+40.0°C | ||
Blast cooling | 0.0°C~+100.0°C | |||
Humidity control | 20%RH~90%RH | |||
Hysteretic amount can be set | 1~40(°C or %RH) | |||
Output contact capacity | 5A/AC250V(electrical independent contact) | |||
Communication interface | RS485,Modbus-RTU protocol | |||
Supportive power supply | voltage | AC 85~265V DC 100~350V | ||
consumption | Basic consumption(≤0.8VA) plus relay consumption(each route≤0.7VA) |
|||
Insulation resistance | ≥100MΩ | |||
Power-Frequency withstand voltage | Power supply and touchable shell metal parts/power supply and other terminals 2kV/1min (AC, RMS) |
|||
Average fault-free time | ≥50000 hours | |||
Working environment (controller) | Temperature | -10°C~+55°C | ||
Humidity | ≤95%RH,No condensation, no corrosive gas | |||
Altitude | ≤2500m |